Site induction and meeting with site personnel. MS4 installed on 10MW turbine and started at 1300hrs Sample 1 taken from 10MW Standard filters Rig switched off at 1900hrs MS4 moved to 5MW turbine Standard filters MS6 moved to 10MW turbine Standard filters
Monday
Tuesday
Rigs switched on at 0700hrs Sample 1 taken from 5MW Rigs switched off at 1900hrs
MS4 and MS6 turned on at 0700hrs Filter changed to 1 micron filters Photograph of dirty filters taken. (See Appendix A&B) 5MW tank agitated Sample 2 taken from 5MW and 10MW turbine Sample taken of clean oil Particle counter fitted to 10MW rig. NAS 6 achieved. (See Appendix B) Rig switched off at 1900hrs MS4 and MS6 turned on at 0700hrs Requested to transfer 400lts of oil into 10MW turbine. 10MW tank agitated. Sample 3 taken from 5MW and 10MW turbine Particle counter fitted to 5MW rig. NAS 5 achieved. (see Appendix A). Rig switched off at 1900hrs Sample taken from 5MW and 10MW tank.