CEPAC SITE SUMMARY REPORT

REPORT COMMENTS ACUSTACK 1 AND 2 - GOOD

• KLEENOIL Filtration cartridge changed, and oil sample taken for independent laboratory analysis

• Both units operating well in a hot but clean environment.

Unit checked & nothing to report

• Attending – Jonathan Brough - Kleenoil

ISO CODE

OIL SAMPLE RESULTS

GOOD

CAUTION

ACTION

BASELINE 08/19

1=19/15/13 2= /

We took a 2 nd sample the following week to check acustack 1 and all ok Both reasonable – A2 is a little wet but current service will have addressed this.

SAMPLED 23/06/20

2=18/16/13 1 ST SAMPLE

1=19/16/13 - THE SAMPLE WAS WET – WE SUSPECT FROM A NEW OIL TOP UP – AND SO RECOMMEND USING FILTER RIG TO CLEAN AS TRANSFERING IN FUTURE

SAMPLED 02/10/20

A1=18/15/12 A2=20/17/14

SAMPLED 24/02/21

A1=18/16/14 A2=20/18/15

A1= STABLE A2= STABLE