DARRINGTON - BULK DIESEL STORAGE TANK

C X - Immediate Action C - Action B - Monitor A - No Action

1ST SAMPLE MAIN TANK

Unit Number Serial Number

KLEENOIL FILTRATION LTD

Customer Name

Make Model

DIESEL STORAGE TANK UNKNOWN FCC DARRINGTON

Address

SHERBURN IN ELMET,WEST YORKSHIRE FENTON LANE,

Location

17/07/2025

Sample Date

Job No

BULK DIESEL STORAGE TANK

Component Lubricant

Received Date

29/07/2025

Diesel Fuel unknown

Ian Burton

Interpreted By

Reported Date

07/08/2025

Fuel Contaminants

Bacteria (Neg / Trace / Pos) In-House

N/T/P

Negative 1 - None Negative

Free Water

-

-

Fungus (Neg / Trace / Pos) In-House

N/T/P

Fuel Physical Tests

Colour - Fuel

In-House

n/a

Yellow

Sulphur

ASTM D5185-97

ppm

64

A - No Action C

Diagnosis: ACTION REQUIRED! THE PARTICLE COUNT (ISO TARGET 18/16/13) CANNOT BE MEASURED DUE TO METALLIC DEBRIS IN THE SAMPLE. ASSUMING THIS IS A REPRESENTATIVE SAMPLE THEN FURTHER STEPS NEED TO BE TAKEN TO REMOVE THIS DEBRIS. WE RECOMMEND THE USE OF A FILTRATION (POLISHING) SYSTEM TO TRY AND CLEAN UP THIS FUEL.

X - Immediate Action C - Action B - Monitor

Fluid and Condition Monitoring Services, Unit 3 Triangle Business Park, Oakwell Way, Birstall, Batley, West Yorkshire, WF17 9LU. Tel: 0113 201 2065 Email: Oillab@finning.co.uk. For more information, or to view your results online, please visit www.fluid-analysis.com This information is supplied for your benefit only and should not be relied on by any third party whatsoever.