DARRINGTON - BULK DIESEL STORAGE TANK

C X - Immediate Action C - Action B - Monitor A - No Action

2ND SAMPLE MAIN TANK

Unit Number Serial Number

KLEENOIL FILTRATION LTD

Customer Name

Make Model

DIESEL STORAGE TANK UNKNOWN FCC DARRINGTON

Address

SHERBURN IN ELMET,WEST YORKSHIRE FENTON LANE,

Location

24/07/2025

Sample Date

Job No

BULK DIESEL STORAGE TANK

Component Lubricant

Received Date

29/07/2025

Diesel Fuel unknown

Ian Burton

Interpreted By

Reported Date

04/08/2025

Fuel Physical Tests

Colour - Fuel

In-House

n/a

Yellow

Sulphur

ASTM D5185-97

ppm

11

A - No Action C

Diagnosis: ACTION REQUIRED! THE PARTICLE COUNT IS RATHER HIGHER THAN THE TARGET (ISO 18/16/13) WHILE ALL OTHER READINGS SEEM FINE. ASSUMING THIS IS A REPRESENTATIVE SAMPLE THEN STEPS NEED TO BE TAKEN TO IMPROVE THE PARTICLE COUNT. WE RECOMMEND THE USE OF A FILTRATION (POLISHING) SYSTEM TO TRY AND CLEAN UP THIS FUEL.

X - Immediate Action C - Action B - Monitor

Fluid and Condition Monitoring Services, Unit 3 Triangle Business Park, Oakwell Way, Birstall, Batley, West Yorkshire, WF17 9LU. Tel: 0113 201 2065 Email: Oillab@finning.co.uk. For more information, or to view your results online, please visit www.fluid-analysis.com This information is supplied for your benefit only and should not be relied on by any third party whatsoever.

Page 2 of 2

Made with FlippingBook Digital Publishing Software